Thermistor curve calculator (Steinhart-Hart and beta)
Fit the Steinhart-Hart equation 1/T = A + B ln R + C (ln R)³ through three resistance and temperature points to convert any coolant or intake air sensor resistance to temperature, compare with the beta model, and see the voltage your ECU input reads.
Result
Planning estimate from the formula below, not a measurement.
How it works
The formula, the method step by step, then a worked example.
1/T = A + B ln R + C (ln R)³ (T in kelvin); β = ln(R₁/R₃) ÷ (1/T₁ − 1/T₃); V_in = V_ref × R ÷ (R + R_pull-up)
- Write the Steinhart-Hart equation at the three points and solve the three linear equations for A, B and C.
- Invert it at the measured resistance to get temperature.
- The beta model uses one exponential constant from two points; it is close between those points and drifts outside them.
- With a pull-up resistor to the reference voltage, the ECU sees a voltage divider.
Worked example
Inputs
- Point 1 temperature
- 41 °F
- Point 1 resistance
- 25415 Ω
- Point 2 temperature
- 77 °F
- Point 2 resistance
- 10021 Ω
- Point 3 temperature
- 95 °F
- Point 3 resistance
- 6545 Ω
- Measured resistance
- 15000 Ω
- ECU pull-up resistor
- 2490 Ω
- Reference voltage
- 5 V
Result
Assumptions and limits
- NTC thermistor (resistance falls as temperature rises), as used in most coolant and intake air sensors.
- Self-heating and lead resistance ignored.
- Fit accuracy depends on the points; use the sensor maker's resistance table.
Related terms
Frequently asked
How do you calculate Steinhart-Hart coefficients?
Measure resistance at three temperatures, write 1/T = A + B ln R + C (ln R)³ at each, and solve the three equations. With 25,415 Ω at 5 °C, 10,021 Ω at 25 °C and 6,545 Ω at 35 °C you get A = 1.1384×10⁻³, B = 2.3245×10⁻⁴ and C = 9.489×10⁻⁸.
What is the difference between beta and Steinhart-Hart?
The beta model uses one constant and is accurate near its two reference points. Steinhart-Hart adds a third term, so it typically stays accurate over a much wider range. Coolant sensors spanning −40 to 130 °C are a good case for Steinhart-Hart.
Why does my ECU need a pull-up resistor value for a temperature sensor?
The ECU measures voltage, not resistance. A pull-up resistor to a reference voltage and the sensor to ground form a divider, V = V_ref × R ÷ (R + R_pull-up). The ECU needs the pull-up value to turn voltage back into resistance and temperature.
Answers draw on the sources below.
Sources
- Calibration curves for thermistors (Steinhart and Hart, 1968) · Deep Sea Research and Oceanographic Abstracts 15(4)
- LDC Note 4: Calibrate Steinhart-Hart Coefficients for Thermistors · Stanford Research Systems
- Automotive Handbook · Robert Bosch GmbH
Spot an error? Tell us.