Solid state relay (SSR)

SSRsolid-state relayMOSFET relaysemiconductor relaycontactless relay

A solid state relay (SSR) is an electronic switch that turns a load on and off with semiconductors instead of moving contacts. A small control current drives an LED or gate driver, which switches a MOSFET, thyristor or triac output. It has no arcing or contact wear, but it drops voltage, makes heat and leaks a little current when off.Medium1585

How it works

Inside a typical solid state relay, the control input lights an infrared LED that is optically coupled to the output stage, so the control side is isolated from the load. The output is a triac or thyristor pair for AC loads, or one or more MOSFETs for DC loads. Packaged units reach roughly 100 A.Medium158

Thyristor and triac outputs only turn off when load current passes through zero, and zero-cross types also wait for a voltage zero to turn on. That softens lamp and motor inrush on AC mains. On DC there is no zero crossing, so a 12 V vehicle circuit needs a MOSFET-output DC relay.Medium153

A conducting semiconductor is not a closed contact. A MOSFET output behaves like a resistance, R_ON, and heats by I² × R_ON, while a thyristor output drops a roughly fixed forward voltage and heats in proportion to current. Either way a high-current SSR needs a heat sink and derating with temperature.Medium15813

Off does not mean open. Every SSR leaks a small current through its output when off, enough to keep an LED lamp or another relay input partly energized. Omron's remedy is a bleeder resistor across the load, and it notes MOSFET outputs suit very small loads directly.Medium53

In vehicles the modern form of the SSR is the smart high-side switch. TI's TPS1H100-Q1 combines a 100 mΩ MOSFET with current limiting, thermal shutdown, an inductive clamp and fault reporting, and leaks no more than 3 µA when off. Power distribution modules group dozens of such channels in place of relays.72

Typical values

Off-state leakage, 12 V smart switch
  • 0.5 µA max at 25 °C77 °F
  • 3 µA at 125 °C257 °F
TI TPS1H100-Q1 at 13.5 V supplySourced7
On-resistance, 12 V smart switch
  • 80 mΩ typical, 100 mΩ max at 25 °C
  • Up to 166 mΩ at 150 °C302 °F
TPS1H100-Q1; resistance rises with temperatureSourced7
Maximum PWM input frequency2kHzTPS1H100-Q1 absolute maximum; each part differsSourced7
Inductive turn-off clamp
  • 50-70 V drain-to-source
  • 70 mJ single pulse
TPS1H100-Q1 internal clampSourced7
Incandescent lamp inrushAbout 10× rated current for 20 msCelduc guidance; Wikipedia cites up to about 14×Sourced · medium312
AC motor starting currentUp to 8× rated current for 1.6 sCelduc AC-53 guidance; DC motors also start near stall currentSourced · medium312
Motorsport PDM channel15 A continuous, 100 A peakBosch PBX 190 high-side channelSourced2

How an ECU uses it

Engine controllers rarely switch big loads directly.

They drive a relay coil or the input of a solid state switch from a low-side or high-side output, and the relay or SSR carries the pump, fan or heater current. Check whether the SSR input expects a positive signal or a ground.Medium176

A power distribution module is effectively a bank of programmable solid state relays. Each channel has its own current limit, retry rule and PWM ability, and the module reports current and faults over CAN, so the ECU or dash sees a failed fan or pump instead of guessing.Medium27

Because a MOSFET SSR switches quickly and does not wear, it can pulse-width modulate a pump or fan for speed control, which a mechanical relay cannot do for long. Stay within the device's PWM limit; TI rates the TPS1H100-Q1 input at 2 kHz maximum.157

How to test it

5 checks, in order.

  1. Confirm the type first. Read the label or datasheet for AC or DC output, load voltage, current rating and input range. An AC triac SSR on a 12 V DC circuit can latch on and never turn off, which looks like a failed relay.Medium153
  2. With the load connected and the input off, measure voltage across the load. A few volts across a high-impedance load such as an LED can be normal leakage. It should fall to near zero with a real load or a bleeder resistor fitted.Medium57
  3. Turn the input on and measure the voltage drop across the SSR output at full load current. Divide the drop by the current to get effective on-resistance and compare it with the datasheet. A drop that keeps rising over several minutes points to overheating.Medium816
  4. Run the load at full current for ten minutes, then check the SSR case temperature with an infrared thermometer. Compare it with the maker's derating curve. A hot SSR without a heat sink is the most common cause of thermal shutdown and early failure.Medium157
  5. Safety
    an SSR can fail shorted and leave the load powered. Fuse the feed to protect the wire, never rely on an SSR alone to isolate a fuel pump or heater for service, and disconnect the battery before working on the load.Medium411

Symptoms and causes

Load stays on or glows dimly when switched off

Likely causes Off-state leakage into a high-impedance load such as LEDs, or an AC triac SSR used on DC

Check Measure load voltage with the input off, then add a bleeder resistor; if the load still runs, confirm the SSR is a DC type.

Medium515

SSR cuts out after several minutes at full load

Likely causes Thermal shutdown from I²R heating, missing heat sink or high ambient temperature

Check Log case temperature and voltage drop; a cut-out that tracks temperature is thermal, not electrical.

715

Load never turns on

Likely causes Input polarity wrong, input voltage below threshold, or output stage failed open after an overload

Check Measure input voltage at the SSR terminals while commanded on; if it is correct and the output drop equals supply voltage, the output is open.

Medium7

Load stuck on regardless of command

Likely causes Output semiconductor failed shorted after inrush, a short circuit or an unclamped inductive spike

Check Disconnect the input; if the load still runs, the output is shorted. Replace it and fix the cause before refitting.

Medium48

In tuning

Size an SSR for inrush, not running current.

A cold lamp or stalled motor draws many times its rated current, and an SSR cannot ride through overload the way relay contacts can. Pick a part whose surge rating covers the inrush, or one with active current limiting.Medium15312

For inductive loads such as pumps, solenoids and fans, confirm the SSR has an internal clamp or fit a flyback diode across the load. Vishay specifies a freewheel diode across inductive loads on its DC SSRs; without one the turn-off spike can exceed the output rating.810

Try it

A
:1

Typical surge multipliers, used only to flag a PDM channel's inrush allowance. Check the load's own data.

%

80% is the common sizing rule: the fuse is 125% of the steady current.

in
%
V
°F
A
A
A

Result

Fuse or current-limit rating20.0 A
Recommended wire (mm²)2.08 14 AWG
Voltage drop with this wire0.37 V
Smallest for ampacity (mm²)1.31 16 AWG, 21.3 A derated
Smallest for voltage drop (mm²)2.08 14 AWG
Estimated start-up surge90 A
Channel load60 %
PDM total load60 %

Start-up surge exceeds the channel rating: check the PDM's inrush time allowance for this channel.

Planning estimate from the formula below, not a measurement.

Open the full pdm channel fuse and wire size calculator →

Common mistakes

Mistake Using an AC triac SSR on a 12 V DC load.

Do instead Use a DC-output MOSFET SSR or a smart high-side switch. A triac has no current zero to turn off at on DC.Medium15

Mistake Mounting a 40 A SSR without a heat sink because the label says 40 A.

Do instead The rating assumes a heat sink. Derate for ambient temperature and check case temperature at full load.Medium158

Mistake Driving LED lamps or another relay input from an SSR without allowing for leakage.

Do instead Add a bleeder resistor or choose a low-leakage MOSFET output so off-state current stays below the load's release current.Medium53

Mistake Skipping the fuse because the SSR has built-in protection.

Do instead Internal limiting protects the device, and a shorted output is not limited at all. Fuse the feed for the wire gauge.Medium711

Myths vs facts

Myth A solid state relay is a drop-in replacement for any mechanical relay.

Fact It is specific to AC or DC and to load type, drops voltage, makes heat and leaks current when off. A five-pin automotive relay also offers a changeover contact that a single SSR output does not.Medium15145

Myth Solid state relays never wear out.

Fact They have no contacts to erode, so switching life is long. Heat cycling, overcurrent and voltage spikes still destroy them, often leaving the output shorted, so thermal design and clamping decide their life.Medium1574

Myth When an SSR is off, the load is disconnected.

Fact Leakage current still flows, and a high-impedance load can show several volts. For service work, isolate the circuit with a fuse pull or battery disconnect.Medium57

Frequently asked

How does a solid state relay work?

A small control current lights an LED or drives a gate circuit inside the relay. That turns on a semiconductor output, a MOSFET for DC or a triac or thyristor pair for AC, which connects the load. With no moving parts, switching is silent, bounce-free and fast.Medium15

Is a solid state relay better than a mechanical relay?

It depends on the job. An SSR wins for fast or frequent switching, PWM speed control, vibration and life. A mechanical relay wins on cost, overload tolerance, near-zero off leakage and lower heat at high current. In cars, smart high-side switches now combine both roles with fuse-like protection.Medium15147

Can a solid state relay switch DC?

Yes, if it is a DC-output type. DC solid state relays use MOSFETs or IGBTs that can turn off at any moment. AC types use triacs or thyristors that only turn off when current crosses zero, so on a DC circuit they can stay latched on.Medium158

Why does my solid state relay get hot?

Its output is a semiconductor, not a metal contact, so load current through its on-resistance or forward drop turns into heat. A MOSFET at 10 A and 10 mΩ dissipates 1 W; at 100 mΩ it dissipates 10 W. High-current SSRs need a heat sink and derating.138

Do solid state relays fail open or closed?

They can fail either way, but a shorted output is a common result of overcurrent, overheating or a voltage spike, leaving the load stuck on. That is why the feed still needs a fuse and why fuel pumps and heaters need an independent way to shut down.Medium411

Sources

Numbered as cited above. Hover or tap a citation chip to preview it.

16 sources
  1. Automotive Handbook, 10th edition (2018) · Robert Bosch GmbH / Wiley · book · retrieved 2026-10-27
  2. PowerBox PBX 190 data sheet 75077387 · Bosch Motorsport · vendor-doc · retrieved 2026-10-27
  3. Application of solid state relays (S/GEN/APPLICATIONS/A) · celduc relais · vendor-doc · retrieved 2026-10-27
  4. Smart power switches (high-side and low-side) product family overview · Infineon Technologies · vendor-doc · retrieved 2026-10-27
  5. FAQ: SSR leakage current and load reset failure (FAQ02155) · OMRON Industrial Automation · vendor-doc · retrieved 2026-10-27
  6. TPL7407L 40-V 7-channel low side driver data sheet (SLRS066) · Texas Instruments · vendor-doc · retrieved 2026-10-27
  7. TPS1H100-Q1 40-V, 100-mOhm single-channel smart high-side power switch data sheet · Texas Instruments · vendor-doc · retrieved 2026-10-27
  8. Design considerations on solid-state relays in DC configuration (Application Note 09, document 80312) · Vishay Semiconductors · vendor-doc · retrieved 2026-10-27
  9. Ampacity · Wikipedia · reference · retrieved 2026-10-27
  10. Flyback diode · Wikipedia · reference · retrieved 2026-10-27
  11. Fuse (electrical) · Wikipedia · reference · retrieved 2026-10-27
  12. Inrush current · Wikipedia · reference · retrieved 2026-10-27
  13. Power MOSFET · Wikipedia · reference · retrieved 2026-10-27
  14. Relay · Wikipedia · reference · retrieved 2026-10-27
  15. Solid-state relay · Wikipedia · reference · retrieved 2026-10-27
  16. Voltage drop · Wikipedia · reference · retrieved 2026-10-27