eFuse (electronic fuse)

eFusee-fuseelectronic circuit breakersolid-state fusesmart fuse

An eFuse is a semiconductor switch that measures its own current and turns off when current exceeds a set limit, protecting the wire and load like a fuse but resetting electronically. Automotive versions combine a MOSFET switch, current sensing, thermal shutdown and diagnostics, and are the building block of solid-state power distribution.325

How it works

A conventional fuse is a metal link that melts when current heats it past its rating, and it must be replaced after it opens.

An eFuse instead uses a power MOSFET as the switch. Control circuitry senses current and switches the MOSFET off when a limit is exceeded, then allows it to be turned back on.563

An eFuse also beats a melting fuse on speed and precision. TI notes a fuse needs fault current far above its rating and takes milliseconds to seconds to open, while an eFuse's fast-trip comparator ends a hard short in under 200 ns, then regulates current at the set limit.7

TI's TPS1H100-Q1 smart high-side switch is an example of the protection features involved: a current limit programmed with an external resistor, thermal shutdown with self-recovery, and detection of open load, short to battery and short to ground. Those diagnostics are reported to a controller.3

If an overload persists, the eFuse heats until thermal shutdown, around 150 °C (302 °F) junction in TI's example. A latch-off version then stays off until commanded; an auto-retry version restarts after cooling by about 12 °C and a 128 ms delay.7

Unlike a melting fuse, an eFuse can apply different rules for different loads: a short delay to tolerate inrush from motors and lamps, a fast trip on a dead short, automatic retries, or a latch-off after repeated faults. Power distribution modules use many such channels in one housing.Medium21

Typical values

Hard-short responseUnder 200 nsFast-trip comparator in TI eFusesSourced7
Fast-trip threshold1.6 × programmed current limitTI eFuse exampleSourced7
Melting fuse responseMilliseconds to secondsDepends on how far current exceeds the ratingSourced7
Auto-retry delay128msTI TPS25942A; latch-off versions stay offSourced7
Thermal shutdownAbout 150 °C junction, 12 °C hysteresis302 °FTPS25942A; TPS1H100-Q1 trips at 175 °C (347 °F)Sourced73
Automotive smart switch limit accuracy
  • Internal 7-13 A
  • External setting ±14-20%
TPS1H100-Q1; ±14% at 1.6 A and aboveSourced3
Motorsport PDM channel ratings
  • 15 A / 100 A peak
  • 25 A / 150 A
  • 40 A / 150 A
Bosch PBX 190 continuous / peakSourced1

How an ECU uses it

In a PDM or modern body controller, each output is an eFuse channel.

Software sets the trip current, the inrush window and the retry count for each load, and reads each channel's measured current to report open loads, overloads and shorts over CAN.Medium13

Current sensing doubles as diagnostics. A fuel pump channel reading low may mean a failed pump or broken wire; one reading high may mean a dragging pump or blocked filter. A melting fuse tells you nothing until it opens.Medium31

Smart high-side switches report current as a small mirror current. TI's TPS1H100-Q1 sources 1/500 of load current on its sense pin, accurate to ±3% above 1 A, which is precise enough to trend pump and fan current over time.3

How to test it

5 checks, in order.

  1. Read each channel's live current and fault status in the PDM or controller software with the load running. Compare with the load's expected current. A channel at zero current with the output commanded on is an open load or a tripped fault.Medium13
  2. Measure voltage at the load connector with the channel on. It should be close to battery voltage. A drop of more than a few tenths of a volt points to wiring or connector resistance, or to a channel sitting in current limit.Medium83
  3. Test trip behavior with a controlled overload, such as a resistive load just above the set limit, not a dead short on a harness you care about. Confirm the channel trips, retries and latches off as configured.Medium7
  4. Check off-state diagnostics if used. With diagnostics enabled, some devices detect an open load while off by watching the output voltage through an external pull-up, so a few volts on a disconnected output can be normal. Check the datasheet before calling it a fault.Medium3
  5. Safety
    an eFuse channel can fail shorted and leave a load powered. Keep a conventional fuse or breaker in the module's main feed near the battery, and give fuel pumps an independent shutdown path.Medium25

Symptoms and causes

Channel trips at start-up but the load runs if retried

Likely causes Inrush exceeds the trip current, or the inrush window is too short

Check Log channel current at switch-on; lengthen the inrush window within wire limits rather than raising the steady limit.

Medium73

Channel trips after minutes of running

Likely causes Thermal limit from high ambient temperature, or load current creeping above the limit

Check Compare logged channel current and module temperature at the moment of the trip.

Medium3

Output dead with no active fault

Likely causes Channel latched off after repeated faults, disabled in configuration, or an open wire

Check Clear latched faults, check configuration, then measure continuity from output pin to load.

Medium71

Load stays on when commanded off

Likely causes Shorted output switch, or the load wire shorted to another powered circuit

Check Unplug the load wire at the module; voltage on the pin with the output off means the channel failed shorted.

Medium2

In tuning

Set each channel's limit to protect the wire first, then the load.

The trip current must stay below what the wire can carry continuously while still allowing the load's normal inrush. Use the wire's current rating for its gauge, insulation and bundle, not just the load's nameplate.Medium43

Safety note

An eFuse protects its own output. The cable feeding a bank of eFuses carries their combined current and still needs a conventional fuse or breaker near the battery.Medium15

Try it

A
:1

Typical surge multipliers, used only to flag a PDM channel's inrush allowance. Check the load's own data.

%

80% is the common sizing rule: the fuse is 125% of the steady current.

in
%
V
°F
A
A
A

Result

Fuse or current-limit rating20.0 A
Recommended wire (mm²)2.08 14 AWG
Voltage drop with this wire0.37 V
Smallest for ampacity (mm²)1.31 16 AWG, 21.3 A derated
Smallest for voltage drop (mm²)2.08 14 AWG
Estimated start-up surge90 A
Channel load60 %
PDM total load60 %

Start-up surge exceeds the channel rating: check the PDM's inrush time allowance for this channel.

Planning estimate from the formula below, not a measurement.

Open the full pdm channel fuse and wire size calculator →

Common mistakes

Mistake Setting the trip current to the load's running current with no inrush allowance.

Do instead Use an inrush window or soft start, and keep the steady limit below the wire's rating.Medium74

Mistake Raising the limit to stop nuisance trips without upsizing the wire.

Do instead The limit protects the wire. Raising it alone moves the failure into the harness.Medium43

Mistake Leaving out the main feed fuse because every output is eFused.

Do instead Fuse the cable from the battery to the module close to the battery.Medium15

Myths vs facts

Myth An eFuse is just a relay with a fuse built in.

Fact It has no moving contacts. The switching element is a MOSFET, and protection comes from current sensing and control logic, which allows programmable limits, retries and diagnostics that a relay and fuse cannot provide.36

Myth An eFuse cannot fail.

Fact Semiconductor switches can fail, sometimes shorted. That is why the upstream feed still needs conventional overcurrent protection and why safety-related loads need a separate shutdown path.Medium25

Myth An eFuse trips at exactly its set current.

Fact Limits have tolerance. The TPS1H100-Q1's internal limit spans 7-13 A and its external limit is accurate to about ±14-20%, so leave margin between normal load current and the trip point.3

Frequently asked

What is an efuse?

An eFuse is an integrated circuit that pairs a power MOSFET with current sensing and control logic. It limits or cuts current during overload, short circuit or overheating, then resets electronically. Automotive versions also report load current and faults, so a PDM can replace fuse and relay pairs.73

How does an electronic fuse work?

It switches the load through a MOSFET and continuously measures current. If current exceeds the programmed limit, or the switch overheats, control circuitry turns the MOSFET off. Depending on configuration it then retries, waits for a command, or latches off, and it can report the fault to a controller.36

What is the difference between an eFuse and a traditional fuse?

A traditional fuse melts and must be replaced; its trip point depends on heating and is fixed. An eFuse switches off electronically, can be reset, can use programmable limits and inrush delays, and reports faults. It costs more and needs a supply and control logic, which a blade fuse does not.Medium532

Does an eFuse reset itself?

Many do. Devices such as the TPS1H100-Q1 recover automatically after thermal shutdown, and system software can retry a channel after a fault. Repeated faults are usually latched off so a hard short does not keep cycling. The behavior depends on the device and how it is configured.3

Can an eFuse replace a fuse in a car?

It can replace a branch fuse and relay pair, which is what power distribution modules do. The main feed from the battery to the module still needs a conventional fuse or breaker, because the eFuse channels do not protect the cable that supplies them.Medium15

Sources

Numbered as cited above. Hover or tap a citation chip to preview it.

  1. PowerBox PBX 190 data sheet 75077387 · Bosch Motorsport · vendor-doc · retrieved 2026-10-27
  2. Smart power switches (high-side and low-side) product family overview · Infineon Technologies · vendor-doc · retrieved 2026-10-27
  3. TPS1H100-Q1 40-V, 100-mOhm single-channel smart high-side power switch data sheet · Texas Instruments · vendor-doc · retrieved 2026-10-27
  4. Ampacity · Wikipedia · reference · retrieved 2026-10-27
  5. Fuse (electrical) · Wikipedia · reference · retrieved 2026-10-27
  6. Power MOSFET · Wikipedia · reference · retrieved 2026-10-27
  7. Basics of eFuses (SLVA862A) · Texas Instruments · vendor-doc · retrieved 2026-10-27
  8. Voltage drop · Wikipedia · reference · retrieved 2026-10-27